Permit Number: TC-COM-0423-01000
Parcel: 13734001D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0423-01000
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2023 Commercial Electrical APPROVED
05/18/2023 Commercial Mechanical APPROVED
05/08/2023 Site Zoning APPROVED
05/12/2023 Site Engineering NOT REQUIRED
05/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/18/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The plumbing calculations note that only one drinking fountain is provided. Per Section1109.5.1, IBC 2018, no fewer than two drinking fountains shall be provided. One fountain shall be provided for wheelchair users and one for standing persons. Exception 1 of Section 1109.5.1, IBC 2018 allows a single drinking fountain with both high and low spouts to be used in lieu of two separate drinking fountains.
2. Show the location of the water fountains on the floor plan. Reference: Section 107.2.1, IBC 2018.
3. Show that the route to the restroom facilities is accessible and does not pass through a storage room. Reference: Section 2902.3.1, IBC 2018.
05/18/2023 Commercial Structural REVIEW COMPLETED Electrical Plans are missing (submit Lighting, Power plan, etc.)
05/04/2023 Fire New Construction REVIEW COMPLETED
04/18/2023 PDSD Application Completeness REVIEW COMPLETED
05/02/2023 Site Landscape REVIEW COMPLETED