Permit Number: TC-COM-0423-00975
Parcel: 141367940

Address:
7355 S WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0423-00975
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT MASTER SET LOCATED AT: STUDO SESSION 518-759-204, TC-COM-0323-00830 (7355 S WILMOT RD Unit:BLDG 19 TUCSON, AZ 85756) WITH REVIEW NOTES TO BE COPIED ON TC-COM-0423-00974 (7355 S WILMOT RD Unit:BLDG 18 TUCSON, AZ 85756), TC-COM-0423-00975 (7355 S WILMOT RD TUCSON, AZ 85756) & TC-COM-0423-00976 (7355 S WILMOT RD TUCSON, AZ 85756)
12/18/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2023 9:27:57 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/23/2023 1:22:51 PM



Mechanical N/A



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/23/2023 11:32:30 AM
Electrical Review
By: Ron Ross PE
Updated the Dog Wash Station location is missing keynote 13 on sheet ES102

The added electrical layout for ‘RAMADA-1’ is detail #4 not #3 as shown on ES103




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 12/17/2023 10:09:49 PM
Second Revision Plumbing Review:
1).Unresolved- Total gas load on plan page P1.1 needs to be updated to reflect new total load -IFGC 402 ** Total Load should be 2085 CFH**

2), Unresolved-Total Gas load on plan P2.2 is incorrect -IFGC 402 ** Total Load should be 2085 CFH**

3). Unresolved-Provide product spec info for the K9000 truBlu dog washer liste on plan page P4.1 , A High hazard Backflow will be required, Per the product website the hand sprayer can be located below flood rim & unit has shampoo & flee bath injection options - IPC 608 ** Backflow info not provided**

4). Resolved-Provide letter from utility authority that allows the pet fountain drain to potentially collect storm water or provide protection on plan page P1.4 -IPC 1101.3

5). Resolved-Dog washer on P1.2 & P4.1 needs hot water -IPC 607.1
12/12/2023 PDSD Application Completeness REVIEW COMPLETED