Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0423-00961
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/04/2023 | Commercial Electrical | APPROVED | |||
05/08/2023 | Commercial Mechanical | APPROVED | |||
05/08/2023 | Commercial Plumbing | APPROVED | |||
05/01/2023 | Site Engineering | NOT REQUIRED | |||
05/08/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/05/2023 | Commercial Structural | REQUIRES RESUBMIT | BUILDING REVIEW: DATE: May 5, 2023 Assuming that you are able to resolve the zoning issues with the Zoning Department & Fire, please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Building Review Section comments were addressed. NOTE: R-3 maximum allowable is 5 clients & R-4 maximum allowable is 10 clients (indicate the number of clients and the type of use you are proposing on your drawings). 1. On the Site Plan show/indicate the Accessible route from drop off location to the entry door complying to ANSI 117A. In an Emergency, show/locate the gathering area where it is safe from danger IBC 310.5. 2. Indicate the clear opening of the doors complying to ANSI 117A. 3. Indicate the clear width of hallways. 4. Show/locate the two grab bars at the Water Closet as well as the two grab bars at the Shower, make sure to indicate the installation of Structural Backer Board for these grab bars. 5. Provide Emergency Escape & Rescue Openings per IRC R310 at every bedroom/sleeping space. On the drawing adjacent to the opening(s), indicate the clear opening for both horizontally and vertically and provide the dimension from the finish floor to the bottom of the opening. Indicate if there are obstacles on either side of the opening. 6. Fire Sprinkler is required and processed as a separate permit. Submit the drawings to the Fire Department for review and approval. They will also conduct inspection, their approval will be required before issuing the Certificate of Occupancy. 7. Electrical work related to installation of Emergency Lights, Lighted Signs, Audible Fire Alarm shall also be reviewed as part of this permit by submitting Electrical drawings. An inspection will be conducted by our inspectors prior to issuance of the Certificate of Occupancy. 8. Any new work must be included as part of this building permit. 9. An Operator's License must be applied for with the State, the absence of this license shall void this building permit. 10. Submit a copy of the State License application as part of this permit. 11. Submit a Narration as to how the facility handles any persons in this facility receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. 12. If you have any questions, contact Justin Eder at Justin.Eder@tucsonaz.gov or at 520-837-4976. | ||
05/02/2023 | Fire New Construction | REQUIRES RESUBMIT | Provide occupancy identification R-4 Condition 1, (NFPA 13D) to match approved fire sprinkler plans. Questions: patricia.shelton@tucsonaz.gov / 520.837.7082 | ||
05/01/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: Wyatt Berger Lead Planner PROJECT: TC-COM-0423-00961 5972 South Rowan Court – R-2 Certificate of Occupancy (1st Review) TRANSMITTAL DATE: May 1, 2023 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. “Halfway house” is not a land use defined within the Tucson Unified Development Code (UDC). Provide a Residential Care Services land use type as defined within UDC Section 11.3.7.D with your next submittal. Additionally, indicate the number of beds proposed as well as show the location of all motor vehicle parking spaces to demonstrate compliance with UDC Table 7.4.4-1. If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951. |
||
04/07/2023 | PDSD Application Completeness | REVIEW COMPLETED |