Permit Number: TC-COM-0423-00951
Parcel: 12218222E

Address:
1137 N DODGE BL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-00951
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2023 Commercial Structural APPROVED
05/01/2023 Site Engineering APPROVED
05/02/2023 Site Zoning APPROVED
05/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/09/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The electrical line diagrams do not show a Main Service Disconnecting means (Main Circuit Breaker) in what appears to be a MLO, All-in-One type Service equipment. Therefore, categorizing the PV interconnection as a Supply Side Interconnection, not a Load Side as indicated in the plan notes. If there is a Main Breaker installed in the All-in-One or service equipment, please show it and its rating in the Line Diagrams. If not, then please apply the requirements of NEC 690.13 and 705.12(A).

Ref; 2018 IBC section 107.2.1, 2017 NEC