Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0423-00945
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/01/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical comments and provide a written response. 1 Indicate conduit and conductor sizes and types for the electrical service riser. 2 Verify that the new panel locations will not require branch circuit extensions and AFCI protection per NEC art 210.12(D). Provide for AFCI protection if applicable. 3 Unit rewiring will require a complete electrical power and lighting floorplan if applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Outdoor Lighting Code, 2018 IECC. |
||
| 04/04/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |