Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0423-00942
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/15/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/14/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 12/12/2023 8:14:47 PM Structural drawings submitted on December 7, 2023 were identical to the drawings previously submitted for permit approval. Structural review was limited to verifying compliance with previous comments submitted on May 1, 2023. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved with Comments Reason: Date Completed : 12/11/2023 12:13:08 PM 1. Several comments have not been resolved and do not comply with the prescriptive and performance requirements of the adopted building codes of the City of Tucson. However, the construction documents have been approved by the City of Tucson building official. See plan review comment response letter. Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 12/7/2023 9:45:52 PM 1. Provide a source capture exhaust system for each bay sheet M2.02 (IMC2018,502.14 (RESOLVED) 2. Provide smoke dampers where ducts penetrate rooms adjacent to corridors that are being served by the same unit in the R2 occupancy sheet M2.03 (IMC2018,607.5.4) (UNRESOLVED) 1. Plan Sheet M2.03 - As per response #2, identify on the plans where they have been updated to show the smoke dampers installed where ducts penetrate rooms adjacent to corridors that are being served by the same unit in the R2 occupancy. 2018 International Building Code Section [A]107.2.1Information on construction documents 3. All fan powered boxes shall shut down when their respective RTU's shut down on a duct smoke activation and shall be stated as such on the RTU schedule notes (IMC2018,606.2.2) (RESOLVED) Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 4/24/2023 4:41:13 PM Electrical Review of Public Safety Complex By: Ron Ross PE Approved with the following comments E0.1 ELECTRICAL DETAILS: Comment only, confirm CAT5 vs CAT6 for lighting control. E1.1 ELECTRICAL SITE PLAN: Could not locate Keynotes 5 and 15. E3.1A POWER PLAN - AREA A: Could not locate Keynotes 1, 2, and 30. E3.2A HVAC/PLUMBING POWER PLAN - AREA A: Missing circuit information on many of the arrowheads. Comment applies to all HVAC sheets. If circuit information can be found elsewhere, provide note on how to reference information. E4.1A SPECIAL SYSTEMS PLAN - AREA A: Could not locate Keynote #3. E4.2A DISPATCH SYSTEM PLAN - AREA A: Could not locate Keynotes 3, C, and D. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved with Comments Reason: Date Completed : 12/12/2023 11:52:25 PM Second Plumbing Review: Ok Subject to Field inspections, See Building official approval of plan set in response narrative Resolved-1). Need to address building plan review comments 3,4,7,8 -IPC 403.1, 1106.2 Resolved-2). The R7 scupper on plan page A6.01 needs an secondary scupper -IPC 1108 Resolved-3). P3.01 Area A 5" roof drain terminations for the 3097 & 3193 sq ft. areas are missing from plan page P2.02 -IPC 1106.2 Resolved-4). Trench Drain system labeled schematic #6 on plan pages P2.02 & P5.02 needs to show a vent for the trench drain Bldg. drain ( suggest 1 combination waste & vent ) -IPC 901.2.1 **Approved By building official see response narrative** Resolved-5). Due to multiple washing machines shown on plan pages P2.02, P2.03, P2.05, P5.01, P5.02 , regardless of type they will need to discharge thru a lint interceptor. -IPC 1003.6 ** Subject to Field inspections & utility authority** Resolved-6). Trench Drain system labeled schematic #1 on plan pages P2.06 & P5.01 needs to show a vent for the trench drain Bldg. drain ( suggest 1 combination waste & vent ) -IPC 901.2.1**Approved By building official see response narrative** Resolved-7). Plan pages P2.06 thru P2.051 have the same 43 notes on each page, remove the notes that don't correlate from each page. -IPC 106.3.1, IFGC 106.3.1 Resolved-8). The notes listed on Plan P2.061 don't correlate to the illustrations. -IPC 106.3.1 Resolved-9). Label the piping systems on plan pages P2.06 thru 2.061 to be able to differentiate the pipes from one another - IPC,IFGC 106.3.1 Resolved-10). S1 sink next to the gas range in the kitchen on plan page P2.05 & Schematic #9 on P5.02 needs to discharge thru a Grease interceptor -IPC 1003.1**Approved By building official see response narrative** Resolved-11), S7 eyewash on plan page P4.02 needs an ASSE 1071 mixing valve -IPC 411.3 Resolved-12). System#1 total DFU load table on Plan page P4.02 doesn't correlate with total DFU load shown on schematic #1 on plan page P5.01. -IPC 709, 710 Resolved-13).Sanitary Vent risers on plan pages P5.01 & P5.02 don't show an illustration for BLDG drain exit of sanitary system #2 -IPC 106.3.1 Resolved-14). In response narrative direct to the page the combustion air & exhaust pipe routing is illustrated for the Gas radiant heaters. -IFGC 304, 503.12). The R7 scupper on plan page A6.01 needs an secondary scupper -IPC 1108 |
||
12/15/2023 | Site Engineering | REQUIRES RESUBMIT | See zoning comment | ||
12/12/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0423-00942 4410 S. Park Av. – R-2 City of Tucson Southside Public Safety Facility - Police and Fire Station (2nd Review) TRANSMITTAL DATE: December 12, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the R-2 zone (UDC 4.7.9). Protective Service (government owned and operated only) is a permitted use in the zone, (Table 4.8-2), subject to Use Specific Standard 4.9.13.F. 1. COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0423-00198 , Zoning cannot approve the building plans until the DP is approved. 2.COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
12/07/2023 | PDSD Application Completeness | REVIEW COMPLETED |