Permit Number: TC-COM-0326-00444
Parcel: 12111214C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0326-00444
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2026 Commercial Building APPROVED
04/09/2026 Commercial Electrical APPROVED
04/09/2026 Site Zoning APPROVED
04/13/2026 Water - PDSD APPROVED
04/06/2026 Site Engineering NOT REQUIRED
04/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/14/2026 Commercial Mechanical REQUIRES RESUBMIT 1. The minimum required ventilation for an occupiable space is based on the occupant density and the activities taking place in the space. The ventilation rate is to be based on Table 403.3.1.1, IMC 2024, or an approved engineering analysis of the specific occupancy type. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces (e.g., therapy office, therapy kitchen, therapy gym, therapy storge, dining, and halls). Reference: Section 403.3.1.1, IMC 2024.
2. Show that the operation of the ventilation system is capable of supplying the outdoor airflow rate required by Section 403.3.1.1, IMC 2024 into the breathing zone of each occupiable space. Reference: Section 403.3.1.1, IMC 2024.
3. Notes on sheet A201 require the existing HVAC system to be rebalanced “…as required for the new wall layout, no new mechanical work.” Show how this is possible given the current arrangement of supply and return diffusers and grilles. Provide the airflow rates that will be required for supplying the required ventilation into the breathing zone of each space. Reference: Sections 403.1 and 608.1, IMC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/13/2026 Commercial Plumbing REQUIRES RESUBMIT 1. Provide specifications for the new sink and faucet located in the therapy kitchen. Reference: Sections 303.4 and 402, IPC 2024.
2. Clarify how the horizontal drain for the new sink will be connected to the existing sanitary waste. Reference: Section 706.1, IPC 2024.
04/16/2026 Fire New Construction REVIEW COMPLETED
04/02/2026 PDSD Application Completeness Express REVIEW COMPLETED