Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0326-00432
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2026 | Commercial Building Standard | APPROVED | |||
| 05/05/2026 | Commercial Electrical Standard | APPROVED | |||
| 05/19/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/19/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | The hot water source consists of the circulating hot water piping. Assuming the domestic water plumbing plan shows the circulating hot water piping being located above the ceiling (i.e. more than ten feet AFF), the hot water drop to the lavatories will be over seven feet long. Revise the design to ensure that the distance from the hot water source to the hot water termination for the public lavatories is no more than 24” for the ½” pipe. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2018 (e.g. 24” for ½” pipe, see room 115).] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 04/28/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |