Permit Number: TC-COM-0326-00426
Parcel: 11619219B

Address:
440 N GRANDE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0326-00426
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2026 Landfill Standard NOT REQUIRED Subject property is outside of boundary of Landfill Ordinance.
04/09/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
04/09/2026 Site Engineering Standard NOT REQUIRED
04/16/2026 Site Zoning Standard NOT REQUIRED Charter school is exempt from zoning
05/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/27/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions about this review, please contact us at CDRC@tucsonaz.gov
Permit address, 440 N GRANDE AV, does not match the address on your plans, 440 N GRANDE AV BLDG 4. If the address on the permit application is incorrect, please submit a request change of address to correct this, if this address is not available, please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify address for building 4.
How to request a change of address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
If the plans are incorrect, please update plans and resubmit.
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
04/17/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00426
ADDRESS/PARCEL: (440 N GRANDE AV Unit:BLDG 1 UNIT 150
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. FACTORY BUILT BUILDING
a. Should this structure be an FBB (Factory Built Structure), the State of Arizona regulates these type structures.
b. Please contact the State of Arizona Department of Housing and inquire about their Factory Built Building Installation Permit as well as their Installation Plan Review Approval.
c. Please contact the State of Arizona Factory Built Buildings using the contact info within this following website Contact Us | Department of Housing.
d. One the state approved, submit the State approved/sealed/dated documents/drawings by uploading it with your response to these comments into your building permit record via the city’s online website. (Note, should the state declines to process…. Please submit the state’s refusal letter containing their letter head allowing the city to process).
2. ON SITE BUILT STRUCTURE
a. This structure appears in city aerial maps in 2016. The issue however, is there are not building permits before or after 2016 for this structure.
b. Please submit a complete set of As-Built drawings that include:
i. Architectural (includes a complete Code Analysis, occupant load calculation, exit width calculation/egress plan, minimum required plumbing fixture calculation, is it sprinklered/not sprinklered, is it alarmed/not alarmed, description of use/what building is being used, etc.)
ii. Mechanical
iii. Electrical
iv. Plumbing
v. Structural
vi. Geotech
vii. NOTE: all of the above drawings are to be sealed/signed/dated by State of Arizona licensed professionals for each discipline.
3. Please respond.
04/14/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0326-00426 (440 N GRANDE AV TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide as-built electrical plans that show compliance with the relevant IEBC chapter 10, and NEC.
2. Electrical floor plan that shows the location of all new, modified and existing electrical work.
3. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
4. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
5. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
6. Show any lighting fixtures being added for both interior and exterior egress and exit lights.
Additional comments may be forthcoming with complete electrical plans.
04/14/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00426
ADDRESS/PARCEL: 440 N GRANDE AV TUCSON, AZ 85745
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:


1. Provide calculations in the code review section to verify that the minimum plumbing facilities required by Table 2902.1, IBC 2024, have been provided. Reference: Sections 1109.5 and 2902.1, IBC 2024.
2. Records do not indicate an approved building permit for Building #4. Based on available mapping data (Pima Maps), the building appears to have been constructed or placed on site between 2014 and 2016. Please clarify and provide documentation demonstrating that the building was properly permitted and approved. Reference: Section 107.2.1, IBC 2024.
3. The occupant load factor for the classrooms is inconsistent between sheets. One sheet indicates a factor of 20, while another indicates a factor of 25. Please revise for consistency or provide clarification.
04/14/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00426
ADDRESS/PARCEL: 440 N GRANDE AV TUCSON, AZ 85745
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:


1. Provide calculations in the code review section to verify that the minimum plumbing facilities required by Table 2902.1, IBC 2024, have been provided. Reference: Sections 1109.5 and 2902.1, IBC 2024.
2. Records do not indicate an approved building permit for Building #4. Based on available mapping data (Pima Maps), the building appears to have been constructed or placed on site between 2014 and 2016. Please clarify and provide documentation demonstrating that the building was properly permitted and approved. Reference: Section 107.2.1, IBC 2024.
3. The occupant load factor for the classrooms is inconsistent between sheets. One sheet indicates a factor of 20, while another indicates a factor of 25. Please revise for consistency or provide clarification.
04/20/2026 Fire New Construction Standard REQUIRES RESUBMIT -The 2024 IFC requires a building fire alarm. Please explain. IFC 907.2.3.
-Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
04/14/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00426
ADDRESS/PARCEL: 440 N GRANDE AV TUCSON, AZ 85745
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:


1. Provide calculations in the code review section to verify that the minimum plumbing facilities required by Table 2902.1, IBC 2024, have been provided. Reference: Sections 1109.5 and 2902.1, IBC 2024.
2. Records do not indicate an approved building permit for Building #4. Based on available mapping data (Pima Maps), the building appears to have been constructed or placed on site between 2014 and 2016. Please clarify and provide documentation demonstrating that the building was properly permitted and approved. Reference: Section 107.2.1, IBC 2024.
3. The occupant load factor for the classrooms is inconsistent between sheets. One sheet indicates a factor of 20, while another indicates a factor of 25. Please revise for consistency or provide clarification.
05/20/2026 Entitlements Standard REVIEW COMPLETED
03/27/2026 PDSD Application Completeness Express REVIEW COMPLETED