Permit Review Detail
Permit Number: TC-COM-0326-00380
Parcel: 137056110
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0326-00380
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2026 | PDSD Application Completeness Express | REQUIRES RESUBMIT | If you have questions regarding this Completeness Review, please contact Maribel Arevalo at maribel.arevalo@tucsonaz.gov 1. One commercial addition/alterations permit required per unit (you will need three permits total) 2. Unit 5306, will need a basic floor plan showing the location of the fire and an inspection report, (At minimum, you will need to submit a letter or inspection report showing that the electrical is safe and no work is required. ) 3. Use this permit for one of the units, you will just need to remove the two extra units from this permit by submitted a request change of address; How to submit a Change of Address: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf 4. Since units 5106 and 5206 were not part of the fire, you will not need to submit plans for these units. At minimum, you will need to submit a letter or inspection report showing that the electrical is safe and no work is required. |