Permit Number: TC-COM-0326-00373
Parcel: 11007232A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0326-00373
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
04/03/2026 Site Engineering Standard NOT REQUIRED
04/06/2026 Site Zoning Standard NOT REQUIRED
04/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact CDRC@tucsonaz.gov
It appears the site plan uploaded lists multiple unit addresses, each individual address requires its own permit. This permit is for the first listed Unit Address of 4067 E GRANT RD UNIT 203 TUCSON, AZ, please start new permits for all other addresses/units. Please apply for new permits for each unit number.
04/08/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Complete Code analysis for the proposed use of the building to include but not be limited to;
A. Construction type
B. Occupancy
C. Sprinklers Yes or No
D. Number of occupants
E. Square foot area
3.Complete site plan
4.Complete dimensioned floor plan, and door sizes, and include the use, occupant load and occupant load for each factor
5.Complete egress plan on the drawings identifying the occupancy classification, occupant load, and the minimum number of required plumbing fixtures for the proposed use. Reference: Sections 302.1, 1004, and 2902.1, 2024 IBC.
6.Please see the City of Tucson Commercial Submittal Requirements https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
7.Please be aware these codes are now being enforced as listed below.
2024 International Building Code (IBC)
2024 International Residential Code (IRC)
2024 International Existing Building Code (IEBC)
2017 ICC A117.1 Accessibility Code (by reference)
2024 International Mechanical Code (IMC)
2024 International Plumbing Code (IPC)
2023 National Electrical Code (NEC)
2024 International Fire Code (IFC)
2024 International Fuel Gas (IFGC)
2018 International Energy Conservation Code (IECC)
City of Tucson/Pima County Outdoor Lighting Code
Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes )




Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/06/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0326-00373 (4067 E GRANT RD Unit:UNIT 203 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide as-built electrical plans that show compliance with the relevant IEBC chapter 10, and NEC.
04/07/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00373
ADDRESS/PARCEL: 4067 E GRANT RD Unit:UNIT 203 TUCSON, AZ 85712
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a code analysis on the drawings identifying the occupancy classification, occupant load, and the minimum number of required plumbing fixtures for the proposed use. Reference: Sections 302.1, 1004, and 2902.1, 2024 IBC.
04/07/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00373
ADDRESS/PARCEL: 4067 E GRANT RD Unit:UNIT 203 TUCSON, AZ 85712
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a code analysis on the drawings identifying the occupancy classification, occupant load, and the minimum number of required plumbing fixtures for the proposed use. Reference: Sections 302.1, 1004, and 2902.1, 2024 IBC.
04/10/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
04/07/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00373
ADDRESS/PARCEL: 4067 E GRANT RD Unit:UNIT 203 TUCSON, AZ 85712
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
03/19/2026 PDSD Application Completeness Express REVIEW COMPLETED