Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0326-00367
Parcel: 12902044A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0326-00367
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2026 Commercial Building Standard APPROVED
03/27/2026 Outdoor Lighting Standard APPROVED
04/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/27/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0326-00367 (2800 E BROADWAY BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Electrical Review:
1. Provide a Grounding Electrode System at the detached structure per NEC 690.47.
2. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure.
3. Show grounding details for the mounting equipment and metal support frame, NEC690.43.
4. Show a complete calculation for determining OCPD and conductor requirements, including temperature and conduit fill derates. Per NEC 690.8(B).
a. Conductor IDs 5 are undersized once conduit fill and temperature derates are applied.
b. Conductors ID 4 may be undersized. Provide ampacity calculations by applying conduit fill and temperature derates.
04/02/2026 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0326-00367 – Commercial Solar Permit
Location: 2800 E BROADWAY BL
Review Date: 4/2/2026

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-06 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.

Drainage Manual Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage…

Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-rete…

Overall, for application submittal requirements, see Administrative Manual Section 2-06

Site Engineering:

1. Site Engineering has reviewed the plans for compliance with development package TD-DEV-0226-00036. Until the development package is approved by all reviewers, site engineering will be unable to approve permit TC-COM-0326-00367.

If you have any questions or concerns, please contact Joe Macaulay at: Joe.Macaulay@tucsonaz.gov
04/06/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-COM-0326-00367 - TD-DEV-0226-00036
2800 E BROADWAY BL
2 New Solar Canopies (2nd Review)

TRANSMITTAL DATE: 4/6/2026


This site is zoned C-1 (UDC Section 4.7.20). Administrative & Professional Office is a permitted use in the C-1 zone subject to UDC use-specific standards 4.9.13.O.


Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

01. COMMENT: Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0226-00036 and although the plans appear to be in compliance, until the DP is approved by all review agencies, Zoning cannot approve the building plan.


For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
04/06/2026 Fire New Construction Standard REVIEW COMPLETED
03/13/2026 PDSD Application Completeness Express REVIEW COMPLETED