Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0326-00364
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2026 | Commercial Building Standard | APPROVED | |||
| 04/02/2026 | Commercial Electrical Standard | APPROVED | |||
| 04/07/2026 | Site Zoning Standard | APPROVED | |||
| 04/06/2026 | Water - PDSD Standard | APPROVED | |||
| 04/02/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction Standard | PENDING ASSIGNMENT | |||
| 04/06/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. “The occupancy type and use has not changed…” is true but the minimum required ventilation for an occupiable space is based on the occupant density and the activities taking place in the space. The ventilation rate for the new juice bar and laundry is to be based on Table 403.3.1.1, IMC 2024, or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2024. 2. Clarify how the vertical riser for the dryer exhaust duct is provided with a means for a cleanout. Reference: Section 504.3, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 04/06/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Provide the specifications for the Wolverine Brass Faucet Model 33493. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson. 2. Verify the calculations for the grease interceptor. Reference: Section 1003.3(B2), IPC 2024, as mended by the City of Tucson If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 04/03/2026 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0326-00364 – Commercial Addition/Alteration Location: 439 N 6TH AV Review Date: 4/3/2026 This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-06 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code. Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage… Design standards for Stormwater Detention and Retention Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-rete… Overall, for application submittal requirements, see Administrative Manual Section 2-06 Site Engineering: 1. This property located at 439 N 6TH AV is located entirely within a FEMA AE floodplain associated with the Tucson Arroyo and will require a separate floodplain use permit with cost estimate. 1. The FPU permit is a separate permit that can be submitted for within the sub-records of this permit. 2. For the submission of the FPU permit, please provide a cost estimate form that will break down the total cost into separate lines, separating labor, materials/equipment, and warranties/fees associated with the project. Ensure to have company/contractor letterhead on the document for proper documentation. 2. Site Engineering will be unable to approve permit TC-COM-0326-00364 until the associated FPU permit is approved. It is recommended that the FPU permit process be started and achieve approval and issuance prior to the resubmission of this permit to ensure no project delays and review overlap. If you have any questions or concerns, please contact Joe Macaulay at: Joe.Macaulay@tucsonaz.gov |
||
| 03/18/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |