| 03/16/2026 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0326-00361 (340 N COMMERCE PARK LP TUCSON, AZ 85745) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Provide main breaker at panel PNL-01: 408.36 Overcurrent Protection. 2. Provide load calculations for panel PNL-01: 408.30 General. 3. Verify conductor sizing for conductor S203, #6 AL. |
||