Permit Number: TC-COM-0326-00354
Parcel: 14139001A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0326-00354
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
Please submit separate PDF files for the engineer’s evaluation and the construction drawings on the next submittal. IBC 107.2.1
1. Provide structural calculations for the proposed ballasted system that demonstrate resistance to both overturning/uplift and lateral sliding forces in accordance with IBC 1605 and ASCE 7, Chapter 29
2. Identify the specific location of all ballast blocks on the construction drawings. If the system relies on interlocking, provide proof that the entire array will not slide as a single unit. For example, show the number of blocks to be at each module. IBC 107.2.1
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/16/2026 PDSD Application Completeness Express REVIEW COMPLETED