Permit Number: TC-COM-0326-00346
Parcel: 12615011C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0326-00346
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2026 Site Zoning Standard APPROVED
04/02/2026 Water - PDSD Standard APPROVED
03/31/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
03/31/2026 Site Engineering Standard NOT REQUIRED
04/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/25/2026 Commercial Building Standard REQUIRES RESUBMIT March 25, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: MAMBO SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00346
Stantec Project Number: 185215066
Stantec File Number: TUC-26-016

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,830 33 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

Sheet M1

1. Transfer grilles are indicated above the ceiling in the head spa and nail/pedicure rooms. These spaces are subject to the ventilation requirements of IMC Table 403.3.1.1, Footnote b, which requires air to be exhausted directly to the outdoors and prohibits recirculation to other spaces. Transfer grilles allowing air movement into adjacent spaces or return plenums are not permitted.

PLUMBING COMMENTS

General

1. Please include in the Plumbing Legend & Symbols the “FM” drainage pipe from the ejector pumps.

Sheet P1

1. The Waste Floor Plan does not indicate that the drainage of the pedicure baths will terminate with an air gap at an indirect waste receptor (floor sink or washer standpipe). Please revise. [Ref. 2024 IPC Sec. 423.3 as amended by City of Tucson]

ELECTRICAL COMMENTS

Sheet E-2

1. The electrical floor plan indicates all ejector pumps with 30A, 1-pole breakers (30/1), while the panel schedule identifies these same circuits as 20A, 1-pole breakers. Please clarify the correct overcurrent protection and revise the plans for consistency. Ensure conductor sizing and equipment ratings are coordinated with the final breaker size per NEC 240.4 and 310.16.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/25/2026 Commercial Electrical Standard REQUIRES RESUBMIT March 25, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: MAMBO SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00346
Stantec Project Number: 185215066
Stantec File Number: TUC-26-016

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,830 33 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

Sheet M1

1. Transfer grilles are indicated above the ceiling in the head spa and nail/pedicure rooms. These spaces are subject to the ventilation requirements of IMC Table 403.3.1.1, Footnote b, which requires air to be exhausted directly to the outdoors and prohibits recirculation to other spaces. Transfer grilles allowing air movement into adjacent spaces or return plenums are not permitted.

PLUMBING COMMENTS

General

1. Please include in the Plumbing Legend & Symbols the “FM” drainage pipe from the ejector pumps.

Sheet P1

1. The Waste Floor Plan does not indicate that the drainage of the pedicure baths will terminate with an air gap at an indirect waste receptor (floor sink or washer standpipe). Please revise. [Ref. 2024 IPC Sec. 423.3 as amended by City of Tucson]

ELECTRICAL COMMENTS

Sheet E-2

1. The electrical floor plan indicates all ejector pumps with 30A, 1-pole breakers (30/1), while the panel schedule identifies these same circuits as 20A, 1-pole breakers. Please clarify the correct overcurrent protection and revise the plans for consistency. Ensure conductor sizing and equipment ratings are coordinated with the final breaker size per NEC 240.4 and 310.16.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/25/2026 Commercial Mechanical Standard REQUIRES RESUBMIT March 25, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: MAMBO SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00346
Stantec Project Number: 185215066
Stantec File Number: TUC-26-016

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,830 33 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

Sheet M1

1. Transfer grilles are indicated above the ceiling in the head spa and nail/pedicure rooms. These spaces are subject to the ventilation requirements of IMC Table 403.3.1.1, Footnote b, which requires air to be exhausted directly to the outdoors and prohibits recirculation to other spaces. Transfer grilles allowing air movement into adjacent spaces or return plenums are not permitted.

PLUMBING COMMENTS

General

1. Please include in the Plumbing Legend & Symbols the “FM” drainage pipe from the ejector pumps.

Sheet P1

1. The Waste Floor Plan does not indicate that the drainage of the pedicure baths will terminate with an air gap at an indirect waste receptor (floor sink or washer standpipe). Please revise. [Ref. 2024 IPC Sec. 423.3 as amended by City of Tucson]

ELECTRICAL COMMENTS

Sheet E-2

1. The electrical floor plan indicates all ejector pumps with 30A, 1-pole breakers (30/1), while the panel schedule identifies these same circuits as 20A, 1-pole breakers. Please clarify the correct overcurrent protection and revise the plans for consistency. Ensure conductor sizing and equipment ratings are coordinated with the final breaker size per NEC 240.4 and 310.16.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/06/2026 Commercial Plumbing Standard REQUIRES RESUBMIT March 25, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: MAMBO SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00346
Stantec Project Number: 185215066
Stantec File Number: TUC-26-016

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,830 33 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

Sheet M1

1. Transfer grilles are indicated above the ceiling in the head spa and nail/pedicure rooms. These spaces are subject to the ventilation requirements of IMC Table 403.3.1.1, Footnote b, which requires air to be exhausted directly to the outdoors and prohibits recirculation to other spaces. Transfer grilles allowing air movement into adjacent spaces or return plenums are not permitted.

PLUMBING COMMENTS

General

1. Please include in the Plumbing Legend & Symbols the “FM” drainage pipe from the ejector pumps.

Sheet P1

1. The Waste Floor Plan does not indicate that the drainage of the pedicure baths will terminate with an air gap at an indirect waste receptor (floor sink or washer standpipe). Please revise. [Ref. 2024 IPC Sec. 423.3 as amended by City of Tucson]

ELECTRICAL COMMENTS

Sheet E-2

1. The electrical floor plan indicates all ejector pumps with 30A, 1-pole breakers (30/1), while the panel schedule identifies these same circuits as 20A, 1-pole breakers. Please clarify the correct overcurrent protection and revise the plans for consistency. Ensure conductor sizing and equipment ratings are coordinated with the final breaker size per NEC 240.4 and 310.16.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/07/2026 Fire New Construction Standard REVIEW COMPLETED
03/16/2026 PDSD Application Completeness Express REVIEW COMPLETED