Permit Number: TC-COM-0326-00340
Parcel: 10510242A

Address:
455 E WETMORE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0326-00340
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2026 Commercial Electrical APPROVED Approved with notes added to the plans.
03/26/2026 Site Zoning APPROVED
03/25/2026 Water - PDSD APPROVED
03/17/2026 Site Engineering NOT REQUIRED
03/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/25/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Please provide an engineering evaluation, prepared by an Arizona registered design professional, verifying that the existing roof structure is capable of supporting the proposed rooftop HVAC unit. If any modifications to the existing roof framing members are required to accommodate the added load, provide complete structural design and calculations prepared and sealed by an Arizona registered engineer. Reference: IBC Section 107.2.7.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/25/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00340
ADDRESS/PARCEL: 455 E WETMORE RD TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The International Mechanical Code, 2024, is the controlling code for this activity, not the 2018 International Mechanical Code. Reference: Section 101.2, IPC 2024. Please correct the code reference in the Outside Air Requirements table.
2. Provide heating and cooling load calculations to justify the heating/cooling capacity of the new 5-ton RTU. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
03/25/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00340
ADDRESS/PARCEL: 455 E WETMORE RD TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Hand sinks in the kitchen area are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Please provide signage at both hand sink locations indicating that the sinks are to be used for handwashing only. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
2. Floor sinks in the kitchen area shall discharge through a grease interceptor. The other floor sink in the “Back of House” near the 3-compartment sink shall discharge through the grease interceptor as well. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
3. Please show all new and existing water piping serving the plumbing fixtures and equipment on the water riser diagram (Detail 4, Sheet DDP1). Additionally, specify the source of hot water on the plans. Reference: Section 107.2.1, 2024 IBC.
03/27/2026 Fire New Construction REVIEW COMPLETED
03/12/2026 PDSD Application Completeness Express REVIEW COMPLETED