Permit Number: TC-COM-0326-00340
Parcel: 10510242A

Address:
455 E WETMORE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0326-00340
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2026 Commercial Building APPROVED
05/19/2026 Commercial Plumbing APPROVED
05/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/19/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00340
ADDRESS/PARCEL: 455 E WETMORE RD TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Per Section C403.3.1 of the 2018 IECC, HVAC equipment shall not be oversized. The output capacity of the heating and cooling equipment shall not be greater than the smallest available equipment size that exceeds the calculated loads determined in accordance with Section C403.1.1. The Equipment Cooling Load Summary indicates a total required cooling load of approximately 18.8 MBH, which appears significantly lower than the capacity of the proposed 5-ton unit. Please provide additional justification for the proposed 5-ton unit or revise the design to utilize equipment sized closer to the calculated load.
05/06/2026 PDSD Application Completeness Express REVIEW COMPLETED