Permit Number: TC-COM-0326-00327
Parcel: 133225020

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0326-00327
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2026 Commercial Building Standard APPROVED
08/14/2026 Commercial Electrical Standard APPROVED
08/21/2026 Commercial Mechanical Standard APPROVED
08/14/2026 Outdoor Lighting Standard APPROVED Approved with notes added to plans.
08/21/2026 Water - PDSD Standard APPROVED
07/31/2026 Site Engineering Standard NOT REQUIRED
08/20/2026 Site Zoning Standard NOT REQUIRED
08/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Provide tempered water for the restroom lavatories with a device conforming to ASSE 1070. Reference: Section 419.5, IPC 2024.
2. Verify that the specified sensor faucet for the restroom lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Verify that the cycle will operate for at least 10 seconds for accessibility. Reference: Section 604.4, IPC 2018 and Section 606.4, ICC/ANSI A117.1-17.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
08/18/2026 Fire New Construction Standard REVIEW COMPLETED
07/30/2026 PDSD Application Completeness Express REVIEW COMPLETED