Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-0326-00327
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2026 | Commercial Building Standard | APPROVED | |||
| 08/14/2026 | Commercial Electrical Standard | APPROVED | |||
| 08/21/2026 | Commercial Mechanical Standard | APPROVED | |||
| 08/14/2026 | Outdoor Lighting Standard | APPROVED | Approved with notes added to plans. | ||
| 08/21/2026 | Water - PDSD Standard | APPROVED | |||
| 07/31/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 08/20/2026 | Site Zoning Standard | NOT REQUIRED | |||
| 08/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/21/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Provide tempered water for the restroom lavatories with a device conforming to ASSE 1070. Reference: Section 419.5, IPC 2024. 2. Verify that the specified sensor faucet for the restroom lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Verify that the cycle will operate for at least 10 seconds for accessibility. Reference: Section 604.4, IPC 2018 and Section 606.4, ICC/ANSI A117.1-17. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 08/18/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 07/30/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |