Permit Number: TC-COM-0326-00315
Parcel: 124190090

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0326-00315
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2026 Site Engineering NOT REQUIRED
03/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/22/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00315
ADDRESS/PARCEL: (1700 E 18TH ST Unit:UNIT 105 TUCSON, AZ 85719)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
The City verified the configuration of this facility using previously approved building permit. Code enforcement also exists against this facility as a result of work being done without a permit.
1. BASED ON THE ABOVE PLEASE DO THE FOLLOWING:
a. Show all work that was done without a permit.
b. Using dash line, show the items that were demolished/removed.
c. Please provide detail drawings illustrating how they were built and what equipment/components are included on the installation.
2. DOORS
a. We also noticed door being removed between the new tenants configurations.
b. If this was done, please indicate which door was removed.
c. Indicate what was used to replace the door.
i. Please provide detail drawings illustrating how this is built.
3. DEMISING WALL
a. Fire rated wall is required between tenants per IBC 402.4.2.1 and IBC 708.
b. Please provide detail drawing at the bottom of the demising wall.
c. Please provide detail drawing at the top of the wall meeting the underside of the roof deck.
4. EGRESS PLAN
a. Please provide an egress plan.
b. Please do indicate the travel distance at the point of exit as well as required exit width, provided exit width and the number of people existing at that point.
5. Provide the Code Analysis.
a. This will be necessary in order to be able to fill the Certificate of Occupancy document of which is being requested.
b. Submit the calculation for the minimum required plumbing fixtures.
c. Submit the exit width calculation.
6. Per the International Building Code 2024, an Arizona licensed registrant shall generate the drawings as submission for the building permit application.
a. Please have an Architect generate the drawings along with his/her seal/signature/date on every Architectural sheets. Please do the same with the Mechanical, Electrical Engineers.
7. Please resubmit.
03/18/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0326-00314 (1700 E 18TH ST Unit:UNIT 104 TUCSON, AZ 85719), TC-COM-0326-00315 (1700 E 18TH ST Unit:UNIT 105 TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide as-built electrical floor plan showing the location of each electrical outlet, receptacle, disconnect, etc.
03/20/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00315
ADDRESS/PARCEL: 1700 E 18TH ST Unit:UNIT 105 TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide mechanical plans showing the existing mechanical system configuration, including the location of all existing equipment and demonstrating that the space is conditioned and meets minimum ventilation requirements. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
03/20/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00315
ADDRESS/PARCEL: 1700 E 18TH ST Unit:UNIT 105 TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide plumbing plans showing all existing plumbing fixtures, equipment, building sewer, water service, and related piping. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a code analysis on the drawings identifying the occupancy classification, occupant load, and the minimum number of required plumbing fixtures for the proposed use. Reference: Sections 302.1, 1004, and 2902.1, 2024 IBC.
03/20/2026 Fire New Construction REQUIRES RESUBMIT The submitted documents are incomplete and a thorough plan review could not be performed. Please be aware that new comments may arise with the next review. Please upload a complete set of drawings.
Questions: patricia.shelton@tucsonaz.gov / 520.837.7082
03/12/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0326-00315
1700 E. 18th Street Unit 105 Tucson, AZ 85719
CofO (1st Review)

TRANSMITTAL DATE: 3/12/2026

The site is zoned I-1 (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Please provide the existing and proposed use as defined by the Unified Development Code and include any associated Use Specific Standards (UDC Table 4.8-5). https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-2105. If a change of use is proposed, a Development Package may be required.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
03/20/2026 Water - PDSD REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00315
ADDRESS/PARCEL: 1700 E 18TH ST Unit:UNIT 105 TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand that will be served by the water meter. Reference: Section 107.2.1, IBC 2024.
03/06/2026 PDSD Application Completeness Express REVIEW COMPLETED