Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2026 Site Zoning APPROVED Interior TI - RNA review not required per proposed scope of work
03/19/2026 Water - PDSD APPROVED
03/25/2026 Design Review NOT REQUIRED Interior remodel only. No RNA review required.
03/11/2026 Site Engineering NOT REQUIRED
04/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2026 Commercial Building REQUIRES RESUBMIT April 2, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: EL RITUAL SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-26-019

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 1,365 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A1

1. Where cold baths are provided in a cluster, at least 5 percent, but not less than one of the cold baths shall be accessible. Please provide means of accessibility in compliance with section 1009 of the ICC A117.1-2017 for one of the cold baths. [Ref. 2024 IBC Sec. 1111.4.14]

2. The turning radius and clear floor space indicates in the sauna do not meet the minimum dimensions of the ICC A117.1-2017. The turning radius indicates 60” but 67” is the required minimum diameter. The clear floor space indicates a length of 48” but the minimum length is 52”. Please revise. [Ref. ICC A117.1-2017 Sec. 304.3.1.1 & 305.3.1]

3. The plans must indicate at least one accessible shower in the Spa area. [Ref. 2024 IBC Sec. 1110.2]

Sheet A3

1. The wood platform stairs in the cold plunge area indicate a tread rise of 9”. The maximum riser height for stairs is 7”. Please revise. [Ref. 2024 IBC Sec. 1011.5.2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please revise the energy lighting design from the 2024 IECC to the currently adopted 2018 IECC.

Sheet E-2

1. The panel schedule for Panel “D” indicates a calculated demand load of 136.9 amps; however, the panel is provided with only a 125A main circuit breaker. Please revise the load calculations, reduce the connected load, or increase the main breaker and feeder conductors to a rating not less than the calculated demand load. The next standard overcurrent device size above 125A is 150A. [Ref. 2023 NEC Art. 215.2(A)(1), 215.3, 240.6(A), and 408.30]

Sheet E-3

1. The 2 power receptacles on the power plan for the sauna room conflict the panel schedule. The panel schedule indicates a receptacle for the sauna room on circuits 31 and 33 as well as another receptacle on circuits 35 and 37. Both receptacles on the power plan indicate circuits 31 and 33. Please revise.

2. The circuits for the water heater on the power plan conflict the panel schedule. The power plan indicates the water heater on circuits 13 and 15 but the panel schedule indicates the water heater on circuits 27 and 29. Please revise.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/02/2026 Commercial Electrical REQUIRES RESUBMIT April 2, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: EL RITUAL SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-26-019

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 1,365 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A1

1. Where cold baths are provided in a cluster, at least 5 percent, but not less than one of the cold baths shall be accessible. Please provide means of accessibility in compliance with section 1009 of the ICC A117.1-2017 for one of the cold baths. [Ref. 2024 IBC Sec. 1111.4.14]

2. The turning radius and clear floor space indicates in the sauna do not meet the minimum dimensions of the ICC A117.1-2017. The turning radius indicates 60” but 67” is the required minimum diameter. The clear floor space indicates a length of 48” but the minimum length is 52”. Please revise. [Ref. ICC A117.1-2017 Sec. 304.3.1.1 & 305.3.1]

3. The plans must indicate at least one accessible shower in the Spa area. [Ref. 2024 IBC Sec. 1110.2]

Sheet A3

1. The wood platform stairs in the cold plunge area indicate a tread rise of 9”. The maximum riser height for stairs is 7”. Please revise. [Ref. 2024 IBC Sec. 1011.5.2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please revise the energy lighting design from the 2024 IECC to the currently adopted 2018 IECC.

Sheet E-2

1. The panel schedule for Panel “D” indicates a calculated demand load of 136.9 amps; however, the panel is provided with only a 125A main circuit breaker. Please revise the load calculations, reduce the connected load, or increase the main breaker and feeder conductors to a rating not less than the calculated demand load. The next standard overcurrent device size above 125A is 150A. [Ref. 2023 NEC Art. 215.2(A)(1), 215.3, 240.6(A), and 408.30]

Sheet E-3

1. The 2 power receptacles on the power plan for the sauna room conflict the panel schedule. The panel schedule indicates a receptacle for the sauna room on circuits 31 and 33 as well as another receptacle on circuits 35 and 37. Both receptacles on the power plan indicate circuits 31 and 33. Please revise.

2. The circuits for the water heater on the power plan conflict the panel schedule. The power plan indicates the water heater on circuits 13 and 15 but the panel schedule indicates the water heater on circuits 27 and 29. Please revise.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/02/2026 Commercial Mechanical REQUIRES RESUBMIT April 2, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: EL RITUAL SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-26-019

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 1,365 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A1

1. Where cold baths are provided in a cluster, at least 5 percent, but not less than one of the cold baths shall be accessible. Please provide means of accessibility in compliance with section 1009 of the ICC A117.1-2017 for one of the cold baths. [Ref. 2024 IBC Sec. 1111.4.14]

2. The turning radius and clear floor space indicates in the sauna do not meet the minimum dimensions of the ICC A117.1-2017. The turning radius indicates 60” but 67” is the required minimum diameter. The clear floor space indicates a length of 48” but the minimum length is 52”. Please revise. [Ref. ICC A117.1-2017 Sec. 304.3.1.1 & 305.3.1]

3. The plans must indicate at least one accessible shower in the Spa area. [Ref. 2024 IBC Sec. 1110.2]

Sheet A3

1. The wood platform stairs in the cold plunge area indicate a tread rise of 9”. The maximum riser height for stairs is 7”. Please revise. [Ref. 2024 IBC Sec. 1011.5.2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please revise the energy lighting design from the 2024 IECC to the currently adopted 2018 IECC.

Sheet E-2

1. The panel schedule for Panel “D” indicates a calculated demand load of 136.9 amps; however, the panel is provided with only a 125A main circuit breaker. Please revise the load calculations, reduce the connected load, or increase the main breaker and feeder conductors to a rating not less than the calculated demand load. The next standard overcurrent device size above 125A is 150A. [Ref. 2023 NEC Art. 215.2(A)(1), 215.3, 240.6(A), and 408.30]

Sheet E-3

1. The 2 power receptacles on the power plan for the sauna room conflict the panel schedule. The panel schedule indicates a receptacle for the sauna room on circuits 31 and 33 as well as another receptacle on circuits 35 and 37. Both receptacles on the power plan indicate circuits 31 and 33. Please revise.

2. The circuits for the water heater on the power plan conflict the panel schedule. The power plan indicates the water heater on circuits 13 and 15 but the panel schedule indicates the water heater on circuits 27 and 29. Please revise.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/02/2026 Commercial Plumbing REQUIRES RESUBMIT April 2, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: EL RITUAL SPA
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0326-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-26-019

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 1,365 10 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A1

1. Where cold baths are provided in a cluster, at least 5 percent, but not less than one of the cold baths shall be accessible. Please provide means of accessibility in compliance with section 1009 of the ICC A117.1-2017 for one of the cold baths. [Ref. 2024 IBC Sec. 1111.4.14]

2. The turning radius and clear floor space indicates in the sauna do not meet the minimum dimensions of the ICC A117.1-2017. The turning radius indicates 60” but 67” is the required minimum diameter. The clear floor space indicates a length of 48” but the minimum length is 52”. Please revise. [Ref. ICC A117.1-2017 Sec. 304.3.1.1 & 305.3.1]

3. The plans must indicate at least one accessible shower in the Spa area. [Ref. 2024 IBC Sec. 1110.2]

Sheet A3

1. The wood platform stairs in the cold plunge area indicate a tread rise of 9”. The maximum riser height for stairs is 7”. Please revise. [Ref. 2024 IBC Sec. 1011.5.2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please revise the energy lighting design from the 2024 IECC to the currently adopted 2018 IECC.

Sheet E-2

1. The panel schedule for Panel “D” indicates a calculated demand load of 136.9 amps; however, the panel is provided with only a 125A main circuit breaker. Please revise the load calculations, reduce the connected load, or increase the main breaker and feeder conductors to a rating not less than the calculated demand load. The next standard overcurrent device size above 125A is 150A. [Ref. 2023 NEC Art. 215.2(A)(1), 215.3, 240.6(A), and 408.30]

Sheet E-3

1. The 2 power receptacles on the power plan for the sauna room conflict the panel schedule. The panel schedule indicates a receptacle for the sauna room on circuits 31 and 33 as well as another receptacle on circuits 35 and 37. Both receptacles on the power plan indicate circuits 31 and 33. Please revise.

2. The circuits for the water heater on the power plan conflict the panel schedule. The power plan indicates the water heater on circuits 13 and 15 but the panel schedule indicates the water heater on circuits 27 and 29. Please revise.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/23/2026 Fire New Construction REVIEW COMPLETED
03/05/2026 PDSD Application Completeness Express REVIEW COMPLETED