Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0326-00307
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/20/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0326-00307 ADDRESS/PARCEL: 410 N TOOLE AV Unit:UNIT 116 TUCSON, AZ 85705 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. EF-2 is significantly below the design airflow indicated on the plans. Please either replace or modify the exhaust fan to achieve the approved design airflow and submit a revised air balance report, or revise the plans and mechanical ventilation design as necessary. Reference: Section 608.1, IMC 2024. |
||
| 10/20/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |