10/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/20/2026 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0326-00307
ADDRESS/PARCEL: 410 N TOOLE AV Unit:UNIT 116 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. EF-2 is significantly below the design airflow indicated on the plans. Please either replace or modify the exhaust fan to achieve the approved design airflow and submit a revised air balance report, or revise the plans and mechanical ventilation design as necessary. Reference: Section 608.1, IMC 2024.