Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0326-00305
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/03/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this Addressing Review, please contact Maribel Arevalo at maribel.arevalo@tucsonaz.gov Complete project address missing from site plan. Please add complete project address to site plan, to include building/unit number if applicable, and resubmit. Step-by-step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |
||
| 03/05/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 03/03/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |