Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0326-00305
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/09/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0326-00305 ADDRESS/PARCEL: 10255 E BROADWAY BL TUCSON, AZ 85748 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Previous comment not addressed [Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.] |
||
| 03/06/2026 | Addressing Validation | REVIEW COMPLETED | |||
| 03/06/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |