Permit Number: TC-COM-0325-00609
Parcel: 11004345J

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0325-00609
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2025 Commercial Electrical Express REQUIRES RESUBMIT Plan Review TC-COM-0325-00609 (3305 N SWAN RD Unit:UNIT 105 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work.
3. Provide complete compliance with the 2018 IECC for the interior lighting including sensors and lighting controls as required. (typically COMcheck).
4. Provide dimensioned structural and framing plans showing the addition of the new door. Include the location of the new door in the plans.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/27/2025 Commercial Mechanical Express REQUIRES RESUBMIT 1. The submitted documents do not adequately show the scope of work for this address or how any intended changes will comply with the adopted building codes. Reference: Section 107.2.1, IBC 2018.
2. A permanently legible imprint of the registrant's seal and signature shall appear on the cover, title, index page, or first sheet of each set of project specifications. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
03/26/2025 PDSD Application Completeness Express REVIEW COMPLETED