Permit Number: TC-COM-0325-00593
Parcel: 140411120

Address:
3380 E ELVIRA RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0325-00593
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2025 Commercial Electrical Standard APPROVED Approved with comment added to plans: 2017 NEC 230.2(E) Identification.
Where a building or structure is supplied by more than one service a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37.
04/21/2025 Commercial Plumbing Standard APPROVED
04/18/2025 Site Zoning Standard APPROVED
04/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/21/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the equipment schedule to provide the weight of the FC units to be installed. IBC 107.2.1
2. Please provide details of the connection of the FC units threaded hanger rod to the existing structure. IBC 107.2.1
3. Provide a sealed evaluation prepared by an Arizona licensed registrant, of the existing structure and its ability to support the additional load of the new FC units. IBC 107.2.7 Further, provide design, calculations and drawings for the strengthening of the existing structure, if necessary.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
04/21/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018.
2. Show that the specified HVAC units comply with the requirements of Section C403, IECC 2018. Reference: Section C502.2.3, IECC 2018.
03/27/2025 PDSD Application Completeness Express REVIEW COMPLETED