Permit Number: TC-COM-0325-00553
Parcel: 13701007V

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0325-00553
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2025 Commercial Electrical Standard APPROVED
05/13/2025 Outdoor Lighting Standard APPROVED
06/04/2025 Site Engineering Standard APPROVED
05/30/2025 Site Zoning Standard APPROVED
05/29/2025 Water - PDSD Standard APPROVED
06/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/29/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. The kiosk does not qualify as an equipment building: it is not for electrical equipment and it has less than 7 Watts per square foot of electrical equipment (110 SF and only a 100 W service). Reference: Section C402.1.2, IECC 2018. [Initial comment: Show how the building envelope complies with the requirements of Section C402, IECC 2018.
2. Equipment buildings are only exempt from the building envelope requirements. Show that the specified AC unit complies with Section C403.3.2, IECC 2018. [Initial comment: Provide specifications for the “Pioneer Ductless” and show how it complies with the requirements of Section C403, IECC 2018..
05/29/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Comment not addressed. How does the downspout discharge enter into the sidewalk scupper? [Initial comment: Clarify how the storm water from the primary roof drain is routed to the sidewalk scupper.]
05/08/2025 PDSD Application Completeness Express REVIEW COMPLETED