Permit Number: TC-COM-0325-00504
Parcel: 12901012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0325-00504
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2025 Commercial Electrical Standard APPROVED MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/31/2025 12:53:56 PM
04/02/2025 Outdoor Lighting Standard APPROVED MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/31/2025 12:53:56 PM
04/14/2025 Water - PDSD Standard APPROVED MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).
04/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).
04/02/2025 Commercial Building Standard REQUIRES RESUBMIT MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).



Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 3/22/2025 2:18:57 AM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds.
Please provide a written response to each comment; updates without a clear response may not be reviewed. If you
have any questions regarding the comments, you may contact me directly. Updates may result in additional
comments.
2. GENERAL - SPECIAL INSPECTIONS: Please have the Registered Design Professional in Responsible Charge of this
project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be
downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
3. GENERAL - MATERIAL SPECIFICATIONS, WOOD CONSTRUCTION: The structural general notes currently do not
specify the required grade and species of typical sawn lumber used in the design of wall studs, beams and headers.
Please update the general notes to include this information.
4. SHEET M301 - MECHANICAL LOADS: Mechanical Sheet M301 calls for the addition of four new kitchen hoods
weighing between 218 lb and 1,270 lb. These loads are currently not called out on Structural Roof Plan S2.3. Per the
structural general notes, under "Limitation of Liability", Note 2, "All imposed loads... are not allowed without specific
approval from the structural engineer unless such loads are specifically shown on the structural documents". Please
confirm that the proposed hoods have been accounted for when evaluating the existing roof framing, and include them
on the structural roof plan.
5. SHEET S4.0 - CONFIRM DESIGN: Detail 206 on Sheet S4.0 appears to mislabel the connection between exterior
"buttress" beams and the interior steel column. Please confirm that the typical shear connection is acceptable at this
location or provide a unique connection.
6. SHEET S4.1 - CONFIRM DESIGN: Detail 230 on Sheet S4.1 shows a proposed steel lintel comprised of (2) L3x3x3/8
angles. Angles are attached to the existing brick via 1/2" through bolts. Due to the angle leg, these bolts are installed
at 1 1/2" from the edge of masonry. This poses a risk of masonry breakout. Please confirm the design and revise the
detail to show the LL3x3 lintel to scale.
7. SHEET S4.1 - CONFLICTING INFORMATION: Detail 224 on Sheet S4.1 gives a glulam beam size that conflicts with
the size called out on plan. Please confirm if the required beam depth shall be 18" per the detail or 21" per Structural
Roof Plan S2.3 (Beam Type "B10").


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 4/1/2025 1:55:10 PM
1. General/Accessible Seating: At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
2. G-004/Occupant load calculation: The occupant load calculation does not include the fixed seating. Provide a detailed occupant load calculation that includes the fixed seating in accordance with 2018 IBC Section 1004.6.
04/02/2025 Commercial Mechanical Standard REQUIRES RESUBMIT MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).


Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 3/31/2025 1:15:39 PM
1. General - Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED certifying agency is acceptable. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements.
2. General - Provide Heat Load Calculations. MUA-1 and MUA-2 provide 5450 CFM of Makeup Air. Grease Hoods
require 7500 CFM of Makeup air. Where is the difference coming from? Show all O/A loads on the calculations. - 2018
IECC Section C403.1.1 Calculation of heating and cooling loads.
3. General - Provide Air Balance Schedule. - 2018 IMC Section 508.1.2 Air Balance
4. General - Confirm MUA-1 and MUA-2 meet the O/A makeup air temperature requirements. - 2018 IMC Section
508.1.1 Makeup air temperature.
04/02/2025 Commercial Plumbing Standard REQUIRES RESUBMIT MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 4/2/2025 12:16:40 AM
First Plumbing Review:
1). Plan Page P102.1: Gas load calculations missing sizing table used & gas system legnth. Add sizing table used & gas
system legnth to gas load calcs. -2018 IFGC 402.3
2). Plan Page A301: Missing lavatory to lavatory center separation distances. Add lavatory to lavatory center separation
distances. -2018 IPC 405.3.1
04/08/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0325-00504
2358 E BROADWAY BL
Site engineering comments are as follows:
1. Until the associated development package, TD-DEV-1124-00315, is approved by all reviewers, this T.I. cannot be approved.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
04/09/2025 Site Zoning Standard REQUIRES RESUBMIT MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719).

CDRC Transmittal

FROM: Loran Shamis, Principal Planner
PDSD Zoning Review Section

PROJECT: TC-COM-0325-00503 and TC-COM-0325-00504 – Stravenue Social
Tenant Improvement (East bldg.) and Shell (West bldg.) (1st review)
Food Service, Alcoholic Beverage Services and Commercial Recreation
2330, 2358 E Broadway Blvd

TRANSMITTAL DATE: April 9, 2025

DUE DATE: April 9, 2025

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has conducted a cursory review of the building permit plan set and while it appears the site plan is consistent with the development package. Zoning cannot approve the building permit plan set until the development packages has been approved.

For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov
04/01/2025 Fire New Construction Standard REVIEW COMPLETED The following requirements apply to the proposed project:
1. Fire Alarm System; A fire alarm system is required by the 2018IFC Chapter 9, additionally: if the occupancy load is 1000 or more, a Emergency voice alarm is required ( IFC 2018 Section 907.2.1.1)
2. Fire Alarm and fire sprinklers requires a separate submittal and permits.
3. Kitchen Hood Fire Suppression Systems requires a separate submittal and permits.
4. Carbon Dioxide system requires an operational permit as well as Nitrogen systems.
03/18/2025 PDSD Application Completeness Express REVIEW COMPLETED In future uploads please include the following statement in your resubmittals to avoid miscommunication on the processing of this plan review: "MASTER SET LOCATED AT: TC-COM-0325-00503 (2330 E BROADWAY BL TUCSON, AZ 85719) WITH REVIEWS TO BE PERFORMED FOR: TC-COM-0325-00504 (2358 E BROADWAY BL TUCSON, AZ 85719)."Please feel free to contact me if you have any questions or concerns regarding these comments. Thank you - Doris Benoit 520.633.9084 Doris.Benoit@Tucsonaz.gov