| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2025 | Site Engineering | NOT REQUIRED | |||
| 04/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/02/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please amend the plans to update the occupant load and occupant load factor(OLF) as follows below. This is a B occupancy with an educational use. IBC 107.2.1 A. The number of occupants is shown for every room and space. IBC 107.2.3 B. The occupant load factor and area are shown for every room and space. IBC 1004.5 C. The occupant load factor used reflects the use/function of the space. IBC 1004.5 For example, It appears that an office use load factor was used instead of an educational use. Please see Table 1004.5 for correct OLF 2. Please update the plumbing fixture analysis after the new occupant load has been determined. IBC 2902.1 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 03/19/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0325-00500 (105 S HOUGHTON RD Unit:UNIT 167 TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide an electrical plan showing any/all electrical work. Note electrical outlets, lights, receptacles, etc.. That are moved, demoed, or added. 2. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4. 3. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/02/2025 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The floor plan shows that 62% of the suite is referred to as a classroom. Why is the occupancy of this suite not counted as education instead of business? Reference: Section 107.2.1, IBC 2018. 2. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018 |
||
| 04/02/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Calculate the number of required plumbing fixtures for the suite based on an education occupancy. Reference: Section 2902.1, IBC 2018. | ||
| 03/28/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0325-00500 105 S HOUGHTON RD Unit: 167. - C-1 Educational Use: Elementary and Secondary (1st Review) TRANSMITTAL DATE: March 28, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-1 zone (UDC 4.7.20). Educational Use: Elementary and Secondary is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.3.D.1 – 7. 1. Clearly demonstrate that the requires of UDC Use Specific Standards 4.9.3.D.1 – 7, are met. A development package (DP) maybe required. The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 03/20/2025 | Fire New Construction | REVIEW COMPLETED | Upgrades of the Fire Alarm or fire Sprinklers System requires a separate permit. city of Tucson Adopted Fire code is the 2024 IFC. | ||