Permit Number: TC-COM-0325-00498
Parcel: 115201420

Address:
1837 W LINDEN ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0325-00498
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/2/2025 4:37:04 AM
04/02/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/2/2025 4:37:19 AM
05/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/2/2025 4:37:51 AM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/2/2025 4:39:40 AM
All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block. Please
include with the resubmittal a separate response narrative, which is numbered or itemized to correspond to each of the noted
plan review comments items.

1. Sheet CV. Indicate the “Inclusive Home Design Ordinance” in the applicable codes listed on this sheet.
2. Sheet GN General Notes. Note on the plans that fire blocking and draft stopping will be provided in accordance with
2018 IBC Section 708.4.2.
3. Sheet GN General Notes. Note on the plans that all interior finishes will be in accordance with 2018 IBC 803.1.
4. Sheet 2 Floor Plan. Label bedroom #5, the information is missing. Include the overall size and ceiling height.
5. Sheet 2 Floor Plan. Provide a life safety/ exit plan on the drawings that indicates the travel distances from the most
remote points for R-4 occupancy as well as the occupant loads. 2018 IBC 1004 and 1017.2. The electrical plan
indicates an exit sign above the exterior door in the office. Clarify if this is to be considered one of the required exits
for the space. If so this door must not lock and the minimum clear exit width must remain clear at all times.
6. Sheet 2.1 Floor Plan. Clarify the turning radius in bath #1. It is not indicated as a 5ft circle turning radius as indicated
in the other bath areas.
7. Sheet 2.1 Floor Plan. Indicate the location of the egress windows in all the rooms used for sleeping purposes. 2018
IBC 1030.1 (2).
8. Sheet 2.1 Floor Plan. Provide information on the skylights to be installed on the window schedule.
9. Sheet 2.1 Floor Plan. Bath #11 and Bath #12 have doors that when opened could block the exit corridor. Doors when
fully opened shall not reduce the required exit width by more than 7”. Doors in any position shall not reduce the
required exit width by more than 1/2. (The noted exceptions are only for R-2 and R-3 occupancies). Clarify that there
is enough area around the doors if partially open will still provide a minimum clear egress path. 2018 IBC 1005.7.1.
10. Sheet 2.1 Floor Plan. Provide construction details for the door headers, window headers and sills, skylights, and the
slump wall infill areas on the plans.
04/02/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/2/2025 4:38:22 AM
Sheet 8 Electrical Plan- Indicate the location of “night lighting” for the common areas and hallways for egress. All rooms and usable floor surfaces in a building shall be equipped with artificial lighting and shall be illuminated at all times that the space
is occupied. 2018 IBC 1008.2.
04/02/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 4/2/2025 4:38:22 AM
Sheet 8 Electrical Plan- Indicate the location of “night lighting” for the common areas and hallways for egress. All rooms and
usable floor surfaces in a building shall be equipped with artificial lighting and shall be illuminated at all times that the space
is occupied. 2018 IBC 1008.2.
04/07/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0325-00498
1837 W LINDEN ST

Site engineering comments are as follows:
1. Please provide rain gutters along the north side of the roofline. Storm water from up to a 10-year rain event may not flow over sidewalks per Technical Standards Manual 7-01.4.3E.
2. The accessible parking space signage shall be mounted no less than 84” above grade per TSM 7-01.9.0_Fig. 3.
3. Please provide waste stream calculations in accordance with TSM Sec 8. Describe proposed method of trash disposal.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
05/02/2025 Site Landscape Standard REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: CONVERTING SFR INTO AN ASSISTED LIVING HOME
ACTIVITY NO: TC-COM-0325-00498
ADDRESS: 1837 W LINDEN ST
ZONING: R-1 RESIDENCE ZONE
LAND USE: ASSISTED LIVING HOME

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape and NPPO Section review comments have been addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. A Zoning Administrator determination is required. Prior to Site Landscape Development Package approval, please make sure Site Zoning comments are addressed.

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
04/02/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-0325-00498
1837 W LINDEN ST. – R-1
Converting SFR into an assisted living home (1st Review)

TRANSMITTAL DATE: April 2, 2025

Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). Residential Care Services, Adult Care or Physical and Behavioral Health Services: Maximum 10 Residents, is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.J. 2.a, 3.a, 4

Per UDC Article 4.9.7.J.4 If licensing is required by the State of Arizona for the use, proof of such licensure is required.

1. Per UDC Article 7.6.4.B and a Zoning Administrators determination when more than four motor vehicle parking spaces are provided the requirements of UDC Articles 7.4.6 & 7.6.4 shall be met. Clearly demonstrate that these requirements are met.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
04/10/2025 Water - PDSD Standard REQUIRES RESUBMIT Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
04/02/2025 Fire New Construction Standard REVIEW COMPLETED
03/17/2025 PDSD Application Completeness Express REVIEW COMPLETED