Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0325-00493
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2025 | Commercial Electrical | APPROVED | |||
| 04/01/2025 | Commercial Mechanical | APPROVED | |||
| 03/27/2025 | Site Zoning | APPROVED | |||
| 04/01/2025 | Water - PDSD | APPROVED | |||
| 03/18/2025 | Outdoor Lighting | NOT REQUIRED | No changes to the outdoor lighting. | ||
| 04/01/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/01/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please amend the plans to replace 2021 IBC code references with 2018 IBC references. Please treat it as a typical note. IBC 107.2.1 For example, sheets S001 & S002 2. Please amend the Required Special Inspections and Tests tables of the Soils and Concrete to be job specific. For example, only list the relevant special inspections and tests for this project. IBC 107.2.1 3. Please provide a list of special inspections for this project IBC 107.2.1 For example, Special inspection of Soils, Special Inspection of Concrete Construction. Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 4. Please provide the structural calculations used to design this project with the next submittal IBC 107.2.7 5. Please amend sheet S102 to indicate the designed weight allowance for each rooftop mechanical unit on the roof framing plan, and we will cross-check with mechanical equipment schedule. IBC 107.2.1 6. Please amend the plans to update the Sheet Index to include all the drawing sheets in this permit’s scope. IBC 107.2.1 For example, sheets M-301, M302, P-001, P-101, P-201are included in the construction drawings and not listed in the Sheet Index. 7. Please amend the plan to include ICC ES REPORT Number and additionally provide manufacturer’s cutsheets and installation guide A list that includes all the drawing sheets in this permit’s scope. IBC 107.2.1 for the RF shielding material with the next submittal. IBC 107.2.1 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 04/01/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the distance from the hot water source to the hot water termination for the relocated lavatory complies with the requirements of Section C404.5, IECC 2018. |
||
| 03/19/2025 | Fire New Construction | REVIEW COMPLETED | Upgrades to fire alarm or fire sprinklers requires a separate permit. City of Tucson Adopted Fire Code is the 2024 IFC with local amendments. |
||
| 03/17/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |