Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0325-00490
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/28/2025 | Commercial Building | APPROVED | |||
| 03/17/2025 | Commercial Electrical | APPROVED | |||
| 03/27/2025 | Commercial Mechanical | APPROVED | |||
| 03/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/27/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Show the drain and vent piping for the floor sink located under the 3-compartment sink on the sanitary and vent floor plan and the riser diagram. Reference: Section 107.2.1, IBC 2018. 2. Provide a metering faucet for the relocated lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Verify that the distance from the hot water source to the hot water termination for the relocated lavatory complies with the requirements of Section C404.5, IECC 2018. |
||
| 03/17/2025 | Fire New Construction | REVIEW COMPLETED | CO2 system requires a separate operational permit and project shall comply with the 2024 IFC with local amendments. | ||
| 03/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |