Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0325-00490
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2025 Commercial Building APPROVED
03/17/2025 Commercial Electrical APPROVED
03/27/2025 Commercial Mechanical APPROVED
03/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/27/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Show the drain and vent piping for the floor sink located under the 3-compartment sink on the sanitary and vent floor plan and the riser diagram. Reference: Section 107.2.1, IBC 2018.
2. Provide a metering faucet for the relocated lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the distance from the hot water source to the hot water termination for the relocated lavatory complies with the requirements of Section C404.5, IECC 2018.
03/17/2025 Fire New Construction REVIEW COMPLETED CO2 system requires a separate operational permit and project shall comply with the 2024 IFC with local amendments.