Permit Number: TC-COM-0325-00481
Parcel: 133148300

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0325-00481
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2025 Site Zoning APPROVED
03/25/2025 Water - PDSD APPROVED
03/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/27/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. T22OT00308
ADDRESS/PARCEL: (5845 E 15TH ST TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.
COMMENTS:
1. NEW FRONT DOOR(S) AND BACK DOOR(S):
a. New front door with sidelite and back door within adjacent tenant, not identified as part of this permit. Add notes to include it within this permit.
b. Front door sidelites, glass shall be safety glass. Please label sidelites as such.
2. BACK DOORS:
a. New back doors directly opening into the back stairwell, no information provided. They are an integral part of this Exit Access Stairway as such Provide door schedule to include the rating of the door complying to the fire rating of the Exit Access Stairway enclosure.
b. Between these two new back doors, ensure to provide a wall detail drawing illustrating the wall assembly used to match the existing exit access stairway enclosure fire rating.
c. Provide Door Head and Jamb detail drawings required complying to the exit access stairway's fire rating.
3. 1 hr DEMISING WALL:
a. Provide a detail drawing of the wall assembly
4. MOP SINK:
a. Locate and label mop sink location on site plan
5. Please resubmit.
03/14/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0325-00481 (1141 N EL DORADO PL Unit:BLDG 3 UNIT 200 TUCSON, AZ 85715)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. >> Electrical sheets are not sealed by an Arizona registered design professional.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/26/2025 Commercial Mechanical REQUIRES RESUBMIT Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018.
03/26/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Revise detail 1/P01 to provide a full-open valve on the discharge side of the check valve. Reference: Section 712.2, IPC 2018.
2. Revise the size of the gravity-flow condensate drain pipes shown on P1.1 to ¾” as required by detail 1/P01. Reference: Section 712.3.5, IPC 2018.
3. Show that the condensate drain system will allow for the clearing of blockages without the need to cut the pipe. Reference: Section 307.2.5, IMC 2018.
03/17/2025 Fire New Construction REVIEW COMPLETED 1.The project shall comply with the 2024 International Fire Code and Local Amendments.
2. Fire Alarm and Fire sprinklers requires a separate permit.
3. Fire extinguishers shall conform to Chapter 9, section 906 Of the 2024 International Fire Code.
03/12/2025 PDSD Application Completeness Express REVIEW COMPLETED