Permit Number: TC-COM-0325-00457
Parcel: 11717023E

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0325-00457
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/10/2025 Commercial Electrical Fast REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0325-00457 (88 E BROADWAY BL Unit:UNIT 120 TUCSON, AZ 85701)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide a conduit fill calculation showing that 4x 10AWG Cu and 6x12 AWG Cu can fit in the provided conduit. Max fill for % for more than 2 conductors is 40%, NEC section 9 Table 1.
2. Clarify breaker size for New Patio Heater Controller. Schemattic Diagram on Sheet E1.0 shows a 20A breaker, while the panel schedule for panel ‘HM1’ shows a 25A breaker.
3. Patio Heater Controller circuit #12 conductors are undersized, as required, NEC 240.4(D)(small conductors).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/17/2025 Commercial Mechanical Fast REQUIRES RESUBMIT Provide a detail of the installation of the radiant heaters including the mounting height and required clearances from combustibles.
03/17/2025 Commercial Plumbing Fast REQUIRES RESUBMIT Revise the natural gas drawing to show the gas load and developed pipe length from the pressure reducing valve for each existing branch and each new appliance of the low pressure gas piping system.
03/10/2025 PDSD Application Completeness Express REVIEW COMPLETED