Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0325-00452
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2025 | Site Engineering Fast | NOT REQUIRED | |||
| 03/07/2025 | Addressing Validation | REQUIRES RESUBMIT | ATTENTION: Parcel addressing issue. The aerial plan shows to be for a duplex, in addition, MapTucson is displaying a second structure on this parcel. The location 1243 E ADELAIDE DR does not have units attached to the address. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the units. After address/units have been added or verified you'll need to submit an address change request to update this record along with a new aerial/site plan that shows the corrected addressing. For questions: Building_Official@tucsonaz.gov | ||
| 03/07/2025 | Commercial Electrical Fast | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0325-00452 (1243 E ADELAIDE DR TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide a Site Plan, Indicate the location and size of buildings, utility meters and lines supporting the alterations, 2018 IBC 107.1. Show the utility lines requiring upgrade or replacement. 2. Clearly mark the location of the meter socket to be replaced. Indicate if it is underground or overhead service conductors. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |