Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0325-00431
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/13/2025 | Commercial Mechanical Fast | APPROVED | |||
| 03/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/13/2025 | Commercial Plumbing Fast | REQUIRES RESUBMIT | Revise the configuration of the natural gas sediment trap, as shown in detail 7/M3.0 to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible). | ||
| 03/06/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |