Permit Number: TC-COM-0325-00431
Parcel: 13323191A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0325-00431
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2025 Commercial Mechanical Fast APPROVED
03/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/13/2025 Commercial Plumbing Fast REQUIRES RESUBMIT Revise the configuration of the natural gas sediment trap, as shown in detail 7/M3.0 to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible).
03/06/2025 PDSD Application Completeness Express REVIEW COMPLETED