Permit Number: TC-COM-0325-00425
Parcel: 11309229B

Address:
885 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0325-00425
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 3/18/2025 8:21:07 PM


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 3/20/2025 2:00:13 AM
03/20/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 3/8/2025 8:00:12 AM
03/25/2025 Site Zoning Standard APPROVED
03/25/2025 Water - PDSD Standard APPROVED
04/01/2025 Site Engineering Standard NOT REQUIRED
04/01/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 3/11/2025 5:55:01 PM
1. E1.0 LIGHTING NOTES AND DETAILS: Lighting Keynotes Hexagons are too dark and #s cannot be easily seen.
Comment applies to lighting sheets too. This will affect the field drawings if sheets are printed out on smaller sheets at
smaller scales.
2. E2.1 WEST POWER PLAN: drawing has some CAD artifacts just outside of the bathrooms that should be removed.
3. E2.2 EAST POWER PLAN: Should identify panels shown on E3.0 Electric Service Diagram.
4. E3.0 ELECTRICAL SCHEDULES: 208 Volt ATS is erroneously attached to 480 volt panel. Need to tie ATS into
correct panel. If the intent is to provide back up to the entire facility, should select a 480 Volt generator and 480 Volt
ATS.
5. E4.0 ELECTRICAL NOTES: Suggestion only, E4.0 should be an electrical cover sheet ie Sheet E0.0.
03/20/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 3/19/2025 4:19:57 PM
1. General - Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED certifying agency is
acceptable. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements.
2. General - Provide Heat Load calculations. Show all O/A loads (cooling/heating) on Heat Load Calculations. Heat loads
with O/A Ventilation rates and HVAC unit design may be substituted for COMcheck and Ventilation Calculations. -
2018 IECC Section C403.1.1 Calculation of heating and cooling loads
03/20/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 3/11/2025 5:55:01 PM
1. E1.0 LIGHTING NOTES AND DETAILS: Lighting Keynotes Hexagons are too dark and #s cannot be easily seen.
Comment applies to lighting sheets too. This will affect the field drawings if sheets are printed out on smaller sheets at
smaller scales.
2. E2.1 WEST POWER PLAN: drawing has some CAD artifacts just outside of the bathrooms that should be removed.
3. E2.2 EAST POWER PLAN: Should identify panels shown on E3.0 Electric Service Diagram.
4. E3.0 ELECTRICAL SCHEDULES: 208 Volt ATS is erroneously attached to 480 volt panel. Need to tie ATS into
correct panel. If the intent is to provide back up to the entire facility, should select a 480 Volt generator and 480 Volt
ATS.
5. E4.0 ELECTRICAL NOTES: Suggestion only, E4.0 should be an electrical cover sheet ie Sheet E0.0.
03/07/2025 Fire New Construction Standard REVIEW COMPLETED
03/05/2025 PDSD Application Completeness Express REVIEW COMPLETED