Permit Number: TC-COM-0325-00425
Parcel: 11309228D

Address:
865 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0325-00425
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2026 Commercial Building Standard APPROVED Structural (S) Reviewer
Madeline Nelson; mnelson@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/12/2026


Building (B) Reviewer
Andrew Frame; AFrame@SAFEbuilt.com
Discipline Status:Approved As Is
Date Completed: 1/16/2026
01/16/2026 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/12/2026
01/16/2026 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Perry Hendershott; phendershott@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/14/2026
REVISED PLAN PLUMBING REVIEW-OK
01/21/2026 Outdoor Lighting Standard APPROVED
01/30/2026 Site Zoning Standard APPROVED
02/02/2026 Water - PDSD Standard APPROVED
02/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/16/2026 Commercial Electrical Standard REQUIRES RESUBMIT Electrical (E) Reviewer
Ron Ross; rross@safebuilt.com
Discipline Status:Denied
Date Completed: 1/13/2026
1.E1.2:Comment only, no floor lighting shown. If no floor lighting is needed, aside from counter lights, E1.2 is
approved.
2.E3.0:480-volt 250 KW Generator is undersized for a 600-amp circuit breaker. The design shall either upsize the
generator or reduce circuit breaker in the generator to a size that provides proper overcurrent protection per 2017 NEC
110.3.A.7 requirements.
3.E3.0: Clarify circuits shown originating from Generator currently shown as MP-25 and MP-27.
02/02/2026 Fire New Construction Standard REVIEW COMPLETED
01/12/2026 PDSD Application Completeness Express REVIEW COMPLETED