Permit Number: TC-COM-0325-00423
Parcel: 12217002B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0325-00423
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2025 Site Zoning APPROVED
03/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0325-00423
ADDRESS/PARCEL: (3457 E SPEEDWAY BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.
COMMENTS:
1. The establishment is shown as having 2,305 sf retail space and proposing No Change.
a. However, the previous Certificate of Occupancy indicates space as having 1,000 sf.
b. Please explain the discrepancy.
2. The floor plan associated with the previous Certificate of Occupancy matches the left side of the current floor plan.
a. Please confirm that the right half of the proposed establishment space is an expansion into the adjacent tenant space.
b. If so, show demolished parts of the space such as the demising wall on your plans. Show everything that were demolished.
c. Identify new construction work that occurred.
3. Fire Sprinkler
a. You identified the allowed area as 9,000 sf for this Mercantile space matching a V-B type of construction and matching row NS (No sprinkler).
b. You identified the maximum exit travel distance as 200 ft matching the table column as without sprinkler.
c. However, your code analysis row Automatic Sprinklers is identified as existing/present.
d. Please confirm whether fire sprinklers and alarm systems are present within the establishment (two tenant spaces, now combined).
4. Storage 107
a. How does the Work Area access the Storage 107.
b. Keynote #5, identifies that entire wall as having Wall Displays.
c. Please show the location of the access whether there is a door or an opening.
5. Drinking Fountain
a. For the business occupancy, water coolers can be substituted for drinking fountains per IBC 2902.1 and IPC 410.1
b. Please locate/label the drinking fountain on the floor plan.
6. ELECTRICAL
a. Confirm that there were no electrical work that was done when they expanded into the adjacent tenant space.
b. If electrical work was done at the time the expansion occurred, please submit the electrical drawings for them.
7. MECHANICAL
a. Confirm that there were no mechanical work that was done when they expanded into the adjacent tenant space.
b. If mechanical work was done at the time the expansion occurred, please submit the mechanical drawings for them.
8. Provide drawings for the following:
a. Ensure that the facility is accessible complying to the ICC/ANSI A117.1 for both Employees and Customers. The tops work surfaces 902.4: shall be 28 inches min and 34 inches max above the floor. Parallel approach 904.3.2: the public use side of the counter surface 36 inches in length minimum. Forward approach 904.3.3: the public use side of the counter surface 30 inches minimum in length. Knee clearance 306.3: between 9 inches and 27 inches above the floor. Maximum depth 306.3.2: extend 25 inches maximum under an element at 9 inches above the floor. Minimum depth 06.3.3: Where clear floor space complying with Section 305, the knee clearance shall be 11 inches minimum in depth at 9 inches above the floor, and 8 inches minimum in depth at 27 inches above the floor.
9. Please resubmit.
03/18/2025 Fire New Construction REVIEW COMPLETED
03/05/2025 PDSD Application Completeness Express REVIEW COMPLETED