Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0325-00413
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2025 | Commercial Building Standard | APPROVED | |||
| 06/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/02/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Natural ventilation cannot be provided for the office, which has an obstructed opening (i.e., a door) between it and the adjacent room. 2. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3.1.1, IMC 2018 or an approved engineering analysis of the specific occupancy type, not Table 1004.5, IBC 2018 . The ventilation requirement for a retail storage area is not based on the number of people in the area, just on 0.12 CFM per square foot of area. 3. Each restroom exhaust fan shall move 70 CFM per water closet if the fan operates intermittently (i.e., operates only when the restroom is occupied). 4. Revise the mechanical ventilation calculations for HVAC systems serving multiple zones per Section 403.3.1.1.2.3, IMC 2018. . [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the new use of the occupied space. Reference: Section 403.3.1.1, IMC 2018.] |
||
| 05/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |