Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2025 Commercial Building Standard APPROVED
06/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/02/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Natural ventilation cannot be provided for the office, which has an obstructed opening (i.e., a door) between it and the adjacent room.
2. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3.1.1, IMC 2018 or an approved engineering analysis of the specific occupancy type, not Table 1004.5, IBC 2018 . The ventilation requirement for a retail storage area is not based on the number of people in the area, just on 0.12 CFM per square foot of area.
3. Each restroom exhaust fan shall move 70 CFM per water closet if the fan operates intermittently (i.e., operates only when the restroom is occupied).
4. Revise the mechanical ventilation calculations for HVAC systems serving multiple zones per Section 403.3.1.1.2.3, IMC 2018.

. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the new use of the occupied space. Reference: Section 403.3.1.1, IMC 2018.]