Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0325-00413
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2025 | Commercial Electrical Standard | APPROVED | |||
| 03/24/2025 | Site Zoning Standard | APPROVED | |||
| 03/28/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 03/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/21/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please provide structural design, calculations and construction drawings prepares by an Arizona licensed design professional used for the design of the new opening in the exterior masonry wall. IBC 107.2.7 2. If Special inspections are required, please provide a statement of special inspections for this project, as well as a list of the required special inspections. IBC 107.2.1, IBC 1704, IBC 1705 Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 3. Please amend plans to show how the accessibility elements have been upgraded. IEBC 305.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are not fully compliant, upgrades shall be required in accordance with IEBC.305.7. For example, the existing toilets do not appear to be fully compliant with the 2009 ICC A117.1 604.3 clearances around the water closet. A. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is used, accessibility upgrades equaling 20% of the cost of the project shall be made. B The stated valuation of the project is $50,000 leaving $10,000 available for Accessibility upgrades. Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 03/25/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Provide calculations to verify that adequate ventilation will be provided for the new use of the occupied space. Reference: Section 403.3.1.1, IMC 2018. | ||
| 03/07/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 03/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |