Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0324-00555
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/07/2024 | Site Engineering | NOT REQUIRED | |||
05/09/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/07/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response 1. “This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by a Registered Electrical Engineer registered in the State of Arizona. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304". |
||
05/07/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Provide plans sealed by an Arizona Registrant that show the extent of repairs to the mechanical systems in the apartment. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. | ||
05/07/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide plans sealed by an Arizona Registrant that show the extent of repairs to the plumbing systems in the apartment. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. | ||
05/09/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Provide plans sealed by an Arizona Registrant that show the extent of damage and repair to the building structure, interior and exterior finishes in the apartment. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
05/07/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-0324-00555 2510 N WINSTEL BL. – O-3 Multifamily - Fire Damage Repair (1st Review) TRANSMITTAL DATE: May 7, 2024 Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed. The site is in the O-3 zone (UDC 4.7.15). Multifamily use is a permitted use in the zone (UDC Table 4.8-3. 1. Provide a complete set of building plans, see Building Code reviewers comments. If you have any questions about this transmittal, contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov. . |
||
04/09/2024 | Fire New Construction | REVIEW COMPLETED | |||
04/08/2024 | PDSD Application Completeness | REVIEW COMPLETED |