Permit Number: TC-COM-0324-00553
Parcel: 11460019C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0324-00553
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2024 Commercial Building APPROVED
04/15/2024 Commercial Electrical APPROVED
04/17/2024 Site Zoning APPROVED
04/16/2024 Site Engineering NOT REQUIRED
04/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/18/2024 Commercial Mechanical REQUIRES RESUBMIT Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed.
1.Please amend plans to comply with Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration states that in addition to signing the seal, the registrant shall include the date the document was sealed.
2. Please provide air balance schedule with next submittal. IMC 403 & IMC 501.3
3. Please amend plans to show the condensate disposal routing on the drawings as well as a detail of the condensate termination. IMC 307
4. Please provide signed and dated COMheck report indicating code compliance for HVAC equipment IECC 503.1

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
04/18/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration states that in addition to signing the seal, the registrant shall include the date the document was sealed.
2. The Fixture Factor Value calculation on sheet P-2 calls for a 1” water meter. What is the size and location of the current water meter serving this suite?
3. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
4. A separate submittal to PC Industrial Wastewater Control is required to verify that the public sewer will be protected from harmful discharges. Contact Lucinda.Hyatt@pima.gov for review and assessment. Reference: Section 1003.1, IPC 2018.
04/05/2024 Fire New Construction REVIEW COMPLETED
04/02/2024 PDSD Application Completeness REVIEW COMPLETED