Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0324-00540
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/11/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Verify the addresses of the three buildings on this parcel of land (e.g. 3004 and 3006 are the addresses of one duplex). Reference: Section 107.2.1, IBC 2018. 2. The inside diameter of 1” Aquapex is only slightly larger than ¾” schedule 40 PVC pipe, the minimum size allowed for water service. A 5/8” water meter is allowed to serve a demand of 20 GPM, which results in an excessive water velocity. Provide water demand calculations for each address. Reference: Section 303.2, 603.1, and 604.3, IPC 2018. |
||
| 03/28/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | Note this permit is only for 3002 E FLORENCE DR the other addresses require a separate permit, one address per permit. For questions you may contact building_official@tucsonaz.gov |