Permit Number: TC-COM-0324-00524
Parcel: 13014019N

Address:
4690 E 29TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0324-00524
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2024 Site Zoning APPROVED
08/16/2024 Site Engineering NOT REQUIRED
08/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0324-00524
ADDRESS/PARCEL: (4690 E 29TH ST TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please do a complete code analysis.
2. Shouldn’t this be an S-1 occupancy?
3. Per your note, this is a masonry construction. Could this be a 5A? You have it as 5.
4. Please include the square footage of building within your code analysis.
5. Show your occupant load calculation for each room making sure that the correct occupancy is chosen and provide the total occupant load
6. Show your minimum plumbing fixtures calculation IBC 2902
7. The covered outdoor tire storage does not have an existing permit. Please submit a complete set of drawings (MEP and Architecturally). Please include the Outdoor Storage new chain link.
8. Identify/label the handicap parking stall and provide the striped accessible route along with the signages.
9. Please respond.
08/13/2024 Fire New Construction REQUIRES RESUBMIT -You list B and M as the occupancy type. It's possible it's also an S1 with all the storage inside the building.
-IFC 3405.4 Tire storage shall be located not less than 50' from lot lines and buildings. It does not appear you meet this requirement on the west and south side.
john.vincent@tucsonaz.gov
5203495581
07/17/2024 PDSD Application Completeness Express REVIEW COMPLETED