Permit Number: TC-COM-0324-00519
Parcel: 124161720

Address:
950 S PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0324-00519
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2024 Commercial Mechanical APPROVED
04/25/2024 Commercial Plumbing APPROVED
04/29/2024 Commercial Structural APPROVED
04/25/2024 Site Zoning APPROVED
04/25/2024 Water - PDSD APPROVED
04/24/2024 Site Engineering NOT REQUIRED
04/29/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/24/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide compliance with the 2018 IECC for the lighting. ComCheck Certificate is acceptable.

2 Drinking fountaian outlet shall be GFI protected per NEC art 422.5(A)(2).

3 Second floor electrical floor plan shows a new 200 -amp sub-panel. The panel schedule calls it existing. Identify this panel in the electrical floor plan, and show it as new or existing, whatever the case, in the Electric Riser Diagram.

4 Distinguish or identify what is new and what is existing for all electrical devices and lighting on the plans. Designate branch circuit and panel for each item on the electrical floor plans and correlate with the associated panel schedule. NEC art 408.4

Ref 2018 IBC section 107.2.1, 2017 NEC
04/01/2024 Fire New Construction REVIEW COMPLETED
03/26/2024 PDSD Application Completeness REVIEW COMPLETED