Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0324-00519
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/25/2024 | Commercial Mechanical | APPROVED | |||
04/25/2024 | Commercial Plumbing | APPROVED | |||
04/29/2024 | Commercial Structural | APPROVED | |||
04/25/2024 | Site Zoning | APPROVED | |||
04/25/2024 | Water - PDSD | APPROVED | |||
04/24/2024 | Site Engineering | NOT REQUIRED | |||
04/29/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/24/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide compliance with the 2018 IECC for the lighting. ComCheck Certificate is acceptable. 2 Drinking fountaian outlet shall be GFI protected per NEC art 422.5(A)(2). 3 Second floor electrical floor plan shows a new 200 -amp sub-panel. The panel schedule calls it existing. Identify this panel in the electrical floor plan, and show it as new or existing, whatever the case, in the Electric Riser Diagram. 4 Distinguish or identify what is new and what is existing for all electrical devices and lighting on the plans. Designate branch circuit and panel for each item on the electrical floor plans and correlate with the associated panel schedule. NEC art 408.4 Ref 2018 IBC section 107.2.1, 2017 NEC |
||
04/01/2024 | Fire New Construction | REVIEW COMPLETED | |||
03/26/2024 | PDSD Application Completeness | REVIEW COMPLETED |