Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0324-00518
Parcel: 10409127C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0324-00518
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2024 Commercial Electrical APPROVED
08/22/2024 Commercial Plumbing APPROVED
08/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/22/2024 Commercial Mechanical REQUIRES RESUBMIT Comment not addressed.[ Initial comment: Verify that the proposed wall louver is capable of admitting sufficient make up air to offset the combined volume of exhaust air from EF-1 and the five clothes dryers. Reference: Sections 304.1 and 504.6, IMC 2018 and Section 304.10, IFGC 2018.]
07/25/2024 PDSD Application Completeness Express REVIEW COMPLETED