Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0324-00516
Parcel: 132131240

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.5

Permit Number - TC-COM-0324-00516
Review Name: COMMERCIAL REVIEW - LIMITED v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2024 Water - PDSD APPROVED
09/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/19/2024 Commercial Mechanical REQUIRES RESUBMIT Comment not resolved. Has the heating/cooling load been recalculated to verify that the existing heat pump can accommodate the load caused by the make-up air? [Second comment: A make-up air unit, MAU-1, is not specified. Has the heating/cooling load been recalculated to include the load caused by the make-up air?] [Initial comment: Revise the Air Balance Calculation using the results of the revised ventilation calculations and only the proposed equipment (e.g. do not include a non-existent make up air unit). Reference: Section 107.2.1, IBC 2018 and Section 501.4, IMC 2018. ]
09/19/2024 Commercial Plumbing REQUIRES RESUBMIT The new pedicure chair does not include backflow protection. Provide backflow protection for the hot and cold water supplies to each chair as required by Section 423.3, IPC 2018, as amended by the City of Tucson. (Note: this nearly identical to the Conditions of Approval from the City of Los Angeles shown on sheet P03.) [Second comment: Provide the 3rd party listing information for the V00275 backflow preventer for the pedicure chairs.] [Initial comment: Provide a detail of the specified pedicure chairs that shows that the installation complies with the requirements of Section 423.3, IPC 2018, as amended by the City of Tucson (e.g. backflow protection, drainage, etc.).]
09/06/2024 PDSD Application Completeness REVIEW COMPLETED