Permit Number: TC-COM-0324-00516
Parcel: 132131240

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.7

Permit Number - TC-COM-0324-00516
Review Name: COMMERCIAL REVIEW - LIMITED v.7
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2024 Commercial Plumbing APPROVED
11/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/26/2024 Commercial Mechanical REQUIRES RESUBMIT Comment not resolved: no new heating/cooling load calculation submitted. [Fourth comment: The heating/cooling load calculation includes only 450 CFM of ventilation air but the make-up air unit is supplying 850 CFM; with a 30F degree temperature difference, this adds 12,000 BTUH to the cooling load. Again, can the existing heat pump accommodate the additional load caused by the make-up air?] [Third comment: Comment not resolved. Has the heating/cooling load been recalculated to verify that the existing heat pump can accommodate the load caused by the make-up air?] [Second comment: A make-up air unit, MAU-1, is not specified. Has the heating/cooling load been recalculated to include the load caused by the make-up air?] [Initial comment: Revise the Air Balance Calculation using the results of the revised ventilation calculations and only the proposed equipment (e.g. do not include a non-existent make up air unit). Reference: Section 107.2.1, IBC 2018 and Section 501.4, IMC 2018. ]
11/18/2024 PDSD Application Completeness Express REVIEW COMPLETED