| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/06/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Revise the configuration of the natural gas sediment trap, as shown in details 1/P.2 and 101/P.2, to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the trap is to be in the bottom opening of the run of the tee, not in the branch of the tee). [Initial comment: Revise the location of the sediment trap to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2018.] | ||